Number of Bus Terminals |
64 |
Max. number of bytes fieldbus |
512 byte input and 512 byte output |
Digital peripheral signals |
512 inputs/outputs |
Analog peripheral signals |
256 inputs/outputs |
Protocol |
open, documented protocol |
Configuration possibility |
via KS2000 |
Bus interface |
RS485 D-sub |
Power supply |
24 V DC (-15 %/+20 %) |
Input current |
70 mA + (total K-bus current)/4, 500 mA max. |
Starting current |
2.5 x continuous current |
Recommended fuse |
≤ 10 A |
Current supply K-bus |
1750 mA |
Power contacts |
max. 24 V DC/max. 10 A |
Electrical isolation |
500 V (power contact/supply voltage/fieldbus) |
Weight |
approx. 170 g |
Operating/storage temperature |
0…+55 °C/-25…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. |
IP20/variable |
Approvals/markings |
CE, UL, ATEX, IECEx, DNV GL |
Ex marking |
ATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc |